Two Zone Detection & Alarm Panel - 2-5/8" Display - 12/24V DC
Each system consists of a monitor panel and up to 14 smoke or heat detectors and/or rate of rise heat detectors connected to each zone (sold separately.)
Features:
- Visual and audible indications of a fire or fault
- Water resistant display
- Voltage and EMI protected
- Reverse polarity protected
Specifications:
- Supply Voltage: 9-32V DC
- Zone Loop Voltage: 24V DC (regardless of input voltage)
- Minimum Alarm Current: 15mA
- Maximum Current Per Zone: 400mA
- Maximum Sensors Per Zone: 8
- EOL Resistor: 5.6kΩ
- Potential Free Transistor Output (Fault, Alarm): 50V max
- Relay Output (Buzzer): 2A